12Df Series ModbusRTU Manual

1 Introduction

The MODBUS is an industrial protocol and is a standard protocol mainly used for PLC communication. MODBUS has several different types - RTU, ASCII, and recently TCP method, and we have applied MODBUS RTU for our actuators.

The industry's de facto serial standard since 1979, MODBUS has enabled millions of automation devices to communicate stably & safely. MODBUS is a request/response protocol and provides services specified by function code. The frame consists of ADU, which is an Application Data Unit, and PDU, which stands for Protocol Data Unit

2 Frame Structure

2.1 Packet Description

The mightyZAP complies with the standard MODBUS-RTU protocol. For the detailed MODBUS RTU specification not covered in this manual, please refer to the MODBUS official website. [https://www.modbus.org/specs.php].

2.1.1 Packet Structure

The maximum transmit/receive packet length of the MODBUS-RTU protocol is 256 Bytes. Therefore, please be careful that the total length of the TX/RX packets does not exceed 256 bytes. MODBUS-RTU communication mode requires an empty space of at least 3.5 Char between the Start and End to distinguish packets as shown in the figure below .

packet Description- Transmit Packet Structure

Address

Fucntion code

Data

Error Check

byte

0

1

2

n-1

n

Data

mightyZAP ID

Function

Data

CRC(MSB)

CRC(LSB)

  • Receive Packet Structure - Normal Response

Address

Fucntion code

Data

Error Check

byte

0

1

2

n-1

n

Data

mightyZAP ID

Function

Data

CRC(MSB)

CRC(LSB)

  • Receive Packet Structure - Abnormal Response

Address

Fucntion code

Data

Error Check

byte

0

1

2

3

4

Data

mightyZAP ID

Function + 0x80

Exception code

CRC(MSB)

CRC(LSB)

2.1.2 Packet Element Description

2.1.2.1 Start
  • This refers to the minimum time to distinguish between different frames.
  • At a communication speed of 57600bps, the transmission time for 1 bit is 0.017msec, and since the start time is 3.5 character time (1 character = 8bit), the minimum start time is 0.486msec.
  • If a frame shorter than the minimum start time is transmitted, it is recognized as continuous data from the previous frame.
2.1.2.2 Address
  • mightyZAP's ID. An identifier to support Serial daisy chain connection in a multi-connection method.
  • With the ID '0', it operates as Broadcasting ID.
2.1.2.3 Function Code
  • The MODBUS-RTU standard function code supported by mightyZAP is as follows.
FunctionCodeDescription
Read Holding Register0x03Reading data from mightyZAP
Write Single Register0x06Setting data value in a specific address of mightyZAP
Write Multiple Register0x10Setting data values ​​in consecutive addresses of mightyZAP
2.1.2.4 Data

Transmission

  • In the case of the Read Register command, the MODBUS address, number of registers, number of bytes, etc. are specified, and in the case of the Write Register command, the MODBUS address, number of bytes, value to be set, etc. are specified.

Reception

  • In the case of the Read Register command, the normal response is that the Node ID and Function Code are received with the same values ​​as when transmitted, and the data is received as the value of each register according to the order of the registers sent during transmission.
  • In the case of the Write Single Register command, the same data as transmitted is received. In the case of Write Multi Register, the starting address and number of registers for which data is to be written are received with the Write Multi Register command.
  • In the case of an abnormal response, it consists of Node ID, Error Code, and Exception Code, and the packet structure of the abnormal response is the same regardless of the function code.
  • In the case of an abnormal response, it consists of Node ID, Error Code, and Exception Code, and the packet structure of the abnormal response is the same regardless of the function code.
2.1.2.5 CRC
  • Enter a 16-bit CRC value and it consists of 2 bytes.
  • The transmission order is lower 1 byte, upper 1 byte.
  • CRC Check Method is CRC-16(X^16 + X^15+X^2+1). For easier calculation, get CRC-16 MODBUS calculator on the Internet.
2.1.2.6 Exception Code
  • Exception codes for abnormal responses to all function codes supported by mightyZAP are defined as follows.
Exception CodeDescription
0x01Illegal FunctionFunction code which are not supported
0x02Illegal Data AddressInvalid register address
0x03Illegal Data ValueInvalid data value
0x04Slave Device FailureDevice failure, parameter setting value error (ready)
0x05AcknowledgeData is not ready (ready)
0x06Slave Device BusyParameter lock status

2.2 Protocol Function Code Description

2.2.1 Read Holding Register (0x03)

Reads the values ​​of a single register (16-bit data) and consecutive register blocks (16-bit data units).

2.2.1.1 Packet Description

Request Frame

AddressFucntion codeStarting AddressQuantity of RegisterCRC
Size(byte)1 byte1 byte2 byte2 byte2 byte
Data0x030x0000 to 0xffff1 to 125(0x7d)

Request OK

AddressFucntion codeByte CountRegister ValueCRC
Size(byte)1 byte1 byte1 byteN\\\* x 2 bytes2 byte
Data0x032 x N\\\*

*N = Quantity of Registers

Request not OK

AddressError codeException CodeCRC
Size(byte)1 byte1 byte1 byte2 byte
Data0x830x01 to 0x06
2.2.1.2 Frame Detail
  • Address Unique ID of mightyZAP from which user wants to read data.
  • Function Code Code 0x03, meaning Read Holding Register command
  • Starting Address Starting address of the data which user wants to read and it consists of 2 bytes.
  • Quantity of Register Size of the data to be read and it consists of 2 bytes.
  • CRC It uses the CRC error check method and consists of 2 bytes.
  • Byte Count Number of responding data.
  • Register Value Data is transmitted in byte units using the address of the request frame as the starting address. Since the data is a WORD type, the size is the same as doubling the number of bytes.
  • Error code The error code is expressed by adding the value 80 (Hex) to the function code. In the case of the Read Holding register, it is transmitted as 83 (Hex).
  • Exception code Detailed error details and it consists of 1 byte.
2.2.1.3 Example

Example #1 - Read Present Position (0x37)

  • Request
AddressFucntion
code
Starting
Address Hi
Starting
Address Lo
Quantity of Register HiQuantity of Register LoCRC LoCRC hi
0x010x030x000x370x000x010x350xC4
  • Request OK -Present Position Data :1000
AddressFucntion
code
Byte
Count
Register
value Hi
Register
value Lo
CRC
Lo
CRC
hi
0x010x030x020x030xe80xB80xFA
  • Request Not OK
AddressError
code
Exception
Code
CRC
Lo
CRC
hi
0x010x830x04CRC
Lo
CRC
hi

Example #2 - Read Present Current (0xD3)

  • Request
AddressFucntion
code
Starting
Address Hi
Starting
Address Lo
Quantity of Register HiQuantity of Register LoCRC LoCRC hi
0x010x030x000x380x000x010x050xC7
  • Request OK -Present Current Data : 300
AddressFucntion
code
Byte
Count
Register
value Hi
Register
value Lo
CRC
Lo
CRC
hi
0x010x030x020x010x2C0xB80x09
  • Request Not OK
AddressError
code
Exception
Code
CRC
Lo
CRC
hi
0x010x830x040x400xF3

2.2.2 Write Single Register

Writes a value to a single register (16-bit data).

2.2.2.1 Packet Description

Request

AddressFucntion codeRegister AddresseRegister ValueCRC
Size(byte)1 byte1 byte2 byte2 byte2 byte
Data0x060x0000 to 0xffff0x0000 to 0xffff

Request OK

AddressFucntion codeRegister AddresseRegister ValueCRC
Size(byte)1 byte1 byte2 byte2 byte2 byte
Data0x060x0000 to 0xffff0x0000 to 0xffff

*N = Quantity of Registers

Request not OK

AddressError codeException CodeCRC
Size(byte)1 byte1 byte1 byte2 byte
Data0x860x01 to 0x06
2.2.2.2 Frame Detail
  • Address Unique ID of mightyZAP where the user wants to write data.
  • Function Code Code 0x06, meaning Write Single Register command.
  • Register Address Address of the data user wants to write and it consists of 2 bytes.
  • Register Value Data value user wants to write and it consists of 2 bytes.
  • CRC It uses the CRC error check method and consists of 2 bytes.
  • Error code The error code is expressed by adding the value 80 (Hex) to the function code, and in the case of the Read Holding register, it is transmitted as 83 (Hex).
  • Exception code Detailed error details and it consists of 1 byte.
2.2.2.2 Example

Example #1 - Write Goal Position (0x38)

  • Request - Goal Position Data : 1000
AddressFucntion
code
Register
Address Hi
Register
Address Lo
Register Value HiRegister Value LoCRC LoCRC hi
0x010x060x000x360x010x2C0x690x89
  • Request OK
AddressFucntion
code
Register
Address Hi
Register
Address Lo
Register Value HiRegister Value LoCRC LoCRC hi
0x010x060x000x360x010x2C0x690x89
  • Request Not OK
AddressError
code
Exception
Code
CRC
Lo
CRC
hi
0x010x860x04CRC
Lo
CRC
hi

2.2.3 Write Multi Register(0x10)

Writes values ​​to consecutive register blocks (16-bit data units).

2.2.3.1 Packet Description

Request

AddressFucntion codeStarting AddressQuantity of RegisterByte CountRegisters ValueCRC
Size(byte)1 byte1 byte2 bytes2 bytes1ByteN\\\* x 2 Bytes2 byte
Data0x100x0000 to 0xffff0x0000 to 1 to 0x007B(123)2 x N\\\*value

Request OK

AddressFucntion codeStarting AddressQuantity of RegisterCRC
Size(byte)1 byte1 byte2 bytes2 bytes2 byte
Data0x100x0000 to 0xffff0x0000 to 1 to 0x007B(123)

*N = Quantity of Registers

Request not OK

AddressError codeException CodeCRC
Size(byte)1 byte1 byte1 byte2 byte
Data0x900x01 to 0x06
2.2.3.2 Frame Detail
  • Address The unique ID of mightyZAP which user wants to write data.
  • Function Code Code 0x10, meaning Write Multi Register command
  • Start Addresse Starting address of the data user wants to write in succession and it consists of 2 bytes.
  • Quantity of Register Size of data user wants to write and it consists of 2 bytes.
  • Byte Count Number of data user wants to write in succession.
  • Registers Value A set of 2 bytes as the value of the data user wants to write. Must add as many data sets as user entered in Byte Count.
  • CRC It uses the CRC error check method and consists of 2 bytes.
  • Error code The error code is expressed by adding 80 (Hex) to the function code, and in the case of the read holding register, it is transmitted as 0x90.
  • Exception code Detailed error details and it consists of 1 byte.
2.2.3.3 Example

Example #1 - Multi Write Goal Speed(0x35) & Goal Current (0x36)

  • Request - Goal Speed Data : 1000, Goal Current Data : 300
AddressFucntion
code
Starting
Address Hi
Starting
Address Lo
Quatity of Register HiQuatity of Register LoByte
Count
Register
Value Hi
Register
Value Lo
Register
Value Hi
Register
Value Lo
CRC LoCRC hi
0x010x100x000x350x000x020x040x030xE80x010x2C0xB00xB9
  • Request OK
AddressFucntion
code
Starting
Address Hi
Starting
Address Lo
Quatity of Register HiQuatity of Register LoCRC LoCRC hi
0x010x100x000x350x000x020x510xC6
  • Request Not OK
AddressError
code
Exception
Code
CRC
Lo
CRC
hi
0x010x830x040x400xF3